The Emphatec InstaLink-PLI combines the features of three terminal blocks used to interface a current loop to a PLC or DCS - two feedthrough terminals and a ground terminal for the shield. But it also includes a make-before-break connector as well as HART® protocol test points. The module is passive and requires no power.
Like many of the Emphatec InstaLink modules the PLI module includes a make-before-break connector that allows a meter to be inserted into the input loop and removed without causing a momentary interruption of the loop.
A test cable is available. A jumpering system is provided for the shield in the transmitter cable and the 24Vdc supply. The jumpers use 0.187” push-on terminals. Jumpers are provided with the module. The Emphatec InstaLink-PLI is one of four Emphatec InstaLink modules designed for 4-20mA loop applications and is the most basic. The others are the CLM current limiter, the GLF ground loop filter and the CLI loop isolator.
Weidmuller Ltd 115 Anderson Avenue, Markham, ON L6E 1A4 Tel: 905.475.0220 Support: 1.800.268.4080 Fax (for Engineering): 905.475.8796 Fax: (for Orders): 905.475.8117 Email: vinesh.kumar@weidmueller.com